American Power Conversion 400V Power Supply User Manual


 
Smart Distribution Panel with ATS 15
ATS Component Details
Motorized switches
The operating lever indicates the present
position of the switch [OFF
(
), trip, or ON
(
)]. This lever is also used to operate the
switch manually. See “Emergency Manual
Operation” on page 22 for proper operating
procedures.
Choose whether the motorized switch is
controlling the input switch using the selector
switch. Use only during emergency manual
operation. See page 21 for more information.
Pressing the trip test button immediately
turns the switch to trip, and, when automatic
operation is enabled, the operating lever
swings to the OFF
(
) position. WARNING:
Do not press this button while load is
connected!
When the motorized switch is in the OFF
(
) position, attach a lock-out tag to the withdrawal
prevention lock for added safety.
The operating lever key is provided in the hardware bag with the ATS. Use the key during
manual operation of the switch to easily control the operating lever.
DANGER
Do NOT operate the motorized switches without following the instructions in
“Emergency Manual Operation” on page 22. Failure to follow proper procedures
could cause personal injury or damage to the equipment.