American Power Conversion AP9207 Power Supply User Manual


 
23
Configuring Share-UPS
Shutdown
modes
To configure Share-UPS, you must choose one of the three
available modes of automatic shutdown of the UPS. Each
shutdown mode is described in this section.
Confirmed
Until Low Battery
•Timer
DIP switches:
Table 5
Select the shutdown mode by using the DIP switches as
described in the following table. (An abbreviated form of
this table also appears on the top panel of Share-UPS.)
Continued on next page
Shutdown Mode
Switch Setting (
=0,
=1)
4321
Confirmed 0 0 0 *
Until Low Batter
y
001
N/A
Timer
2 min. 0 1 0
N/A
5 min. 0 1 1
N/A
10 min. 1 0 0
N/A
15 min. 1 0 1
N/A
30 min. 1 1 0
N/A
Soft Timer 1 1 1
N/A
* Server on
Advanced Port
Await
Confirmation
0000
Treat as
Confirmed
0001
Table 5: DIP switches