27
Configuring Share-UPS
continued
Soft timer
The soft timer allows you to set a custom duration for the
timer, from 0 to 99 minutes. One of the DIP switch settings
in Timer shutdown mode enables the soft timer, whose
default is 60 minutes. To change the soft timer duration, use
the Share-UPS Settings menu. See “Share-UPS Settings
menu: Figure 8,” on page 40.
Completing the
configuration
After you set the DIP switches, perform the following steps
in the order given.
1 If you want to change Share-UPS settings: Com-
plete the configuration of Share-UPS by accessing
the Share-UPS Settings menu. For information on
how to connect to the Share-UPS menu system,
see “Using the Management Port” on page 29.
2 If configuring multiple Share-UPS units: repeat
step 2 for each unit, if applicable. You must con-
figure each Share-UPS unit identically.
3 Test the configuration. See “Testing Share-UPS,”
on page 28.
Continued on next page