Delta Electronics VFD-EL Power Supply User Manual


 
Chapter 4 Parameters|
4-62 Revision August 2008, 2ELE, V1.02
01011 0
Weights
Bit
0=N.O
1=N.C
MI1
MI2
MI3
MI4
MI5
MI6
The setting value
= bit5x2 +bit4x2 +bit2x2
542
= 1x2 +1x2 +1x2
542
=32+16+4
Setting 04.09
=52
NOTE:
2 =16384 2 =8192 2 =4096 2 =2048 2 =1024
2 =512 2 =256 2 =128 2 =64 2 =32
2 =16 2 =8 2 =4 2 =2 2 =1
14 13 12 11 10
98765
4321 0
This parameter is to delay the signals on digital input terminals. 1 unit is 2 msec, 2 units are 4
msec, etc. The delay time is to debounce noisy signals that could cause the digital terminals to
malfunction.
04.26 Display the Status of Multi-function Input Terminal
Settings Read Only Factory setting: ##
Display Bit0: MI1 Status
Bit1: MI2 Status
Bit2: MI3 Status
Bit3: MI4 Status
Bit4: MI5 Status
Bit5: MI6 Status
The multi-function input terminals are falling-edge triggered. For standard AC motor drive,
there are MI1 to MI6 and Pr.04.26 will display 63 (111111) for no action.
12345 0
0=Active
1=off
MI1
MI2
MI3
MI4
MI5
MI6
Weights
Bit
04.10
Digital Terminal Input Debouncing Time
Unit: 2 msec
Settings
1 to 20
Factory Setting: 1