Delta Electronics VFD-EL Power Supply User Manual


 
Chapter 4 Parameters|
Revision August 2008, 2ELE, V1.02 4-41
40%
50%
60%
For 460V Series
80%
90%
100%
70%
Carrier
Frequenc
y
R
a
t
e
d
C
u
r
r
e
n
t
(
%
)
2kHz
4kHz 8kHz
10kHz
12kHz
6kHz
50 with mountin
g
method A
40 with mountin
g
method B
25 with mountin
g
method B
40%
50%
60%
For 115V/230V Series
80%
90%
100%
2kHz
4kHz 8kHz
10kHz
12kHz
6kHz
70%
R
a
t
e
d
C
u
r
r
e
n
t
(
%
)
Carrier
Frequenc
y
50 with mounting method A
40 with mounting method B
35 with mounting method A
25 with mountin
g
method B
02.04 Motor Direction Control
Factory Setting: 0
Settings 0 Forward/Reverse operation enabled
1 Reverse operation disabled
2 Forward operation disabled
This parameter is used to disable one direction of rotation of the AC motor drive direction of
rotation.
02.05 Line Start Lockout
Factory Setting: 1
Settings 0 Disable. Operation status is not changed even if operation
command source Pr.02.01 is changed.
1 Enable. Operation status is not changed even if operation command
source Pr.02.01 is changed.
2 Disable. Operation status will change if operation command source
Pr.02.01 is changed.
3 Enable. Operation status will change if operation command source
Pr.02.01 is changed.
This parameter determines the response of the drive upon power on and operation command
source is changed.
Pr.02.05 Start lockout (Run when power is ON)
Operation status when operation
command source is changed
0 Disable (AC motor drive will run) Keep previous status
1 Enable (AC motor drive doesn’t run) Keep previous status
2 Disable (AC motor drive will run)
Change according to the new
operation command source
3 Enable (AC motor drive doesn’t run)
Change according to the new
operation command source