Delta Electronics VFD-EL Power Supply User Manual


 
Chapter 4 Parameters|
Revision August 2008, 2ELE, V1.02 4-7
Parameter Explanation Settings
Factory
Setting
Customer
0: by Current Freq Command
1: by Zero Freq Command
02.14
Initial Frequency
Selection (for
keypad & RS485)
2: by Frequency Display at Stop
0
02.15
Initial Frequency
Setpoint (for keypad
& RS485)
0.00 ~ 600.0Hz 60.00
02.16
Display the Master
Freq Command
Source
Read Only
Bit0=1: by First Freq Source (Pr.02.00)
Bit1=1: by Second Freq Source (Pr.02.09)
Bit2=1: by Multi-input function
##
02.17
Display the
Operation
Command Source
Read Only
Bit0=1: by Digital Keypad
Bit1=1: by RS485 communication
Bit2=1: by External Terminal 2/3 wire mode
Bit3=1: by Multi-input function
##
02.18
User-defined Value
2 Setting
0 to Pr.00.13 0
02.19
User-defined Value
2
0 to 9999 ##
Group 3 Output Function Parameters
Parameter Explanation Settings
Factory
Setting
Customer
0: No function
1: AC drive operational
2: Master frequency attained
3: Zero speed
4: Over torque detection
5: Base-Block (B.B.) indication
6: Low-voltage indication
7: Operation mode indication
8: Fault indication
9: Desired frequency attained
03.00 Multi-function
Output Relay (RA1,
RB1, RC1)
10: Terminal count value attained
8