Delta Electronics VFD-EL Power Supply User Manual


 
Chapter 4 Parameters|
Revision August 2008, 2ELE, V1.02 4-67
Group 6: Protection Parameters
06.00 Over-Voltage Stall Prevention Unit: 0.1
Settings 115V/230V series 330.0 to 410.0V Factory Setting: 390.0
460V series 660.0 to 820.0V Factory Setting: 780.0
0 Disable Over-voltage Stall Prevention (with brake unit or
brake resistor)
During deceleration, the DC bus voltage may exceed its Maximum Allowable Value due to
motor regeneration. When this function is enabled, the AC motor drive will not decelerate
further and keep the output frequency constant until the voltage drops below the preset value
again.
Over-Voltage Stall Prevention must be disabled (Pr.06.00=0) when a brake unit or brake
resistor is used.
NOTE
With moderate inertia load, over-voltage stall prevention will not occur and the real deceleration time
will be equal to the setting of deceleration time. The AC drive will automatically extend the
deceleration time with high inertia loads. If the deceleration time is critical for the application, a brake
resistor or brake unit should be used.
high voltage at DC side
over-voltage
detection level
output
frequency
time
Deceleration characteristic
when Over-Voltage Stall
Prevention enabled
Frequency Held
time
previous deceleration time
actual time to decelerate to stop when over-voltage
stall prevention is enabled