Delta Electronics VFD-EL Power Supply User Manual


 
Revision August 2008, 2ELE, V1.02
Appendix A Specifications
There are 115V, 230V and 460V models in the VFD-EL series. For 115V models, it is 1-phase
models. For 0.25 to 3HP of the 230V models, there are 1-phase/3-phase models. Refer to following
specifications for details.
Voltage Class 115V Class
Model Number VFD-XXXEL 002 004 007
Max. Applicable Motor Output (kW) 0.2 0.4 0.75
Max. Applicable Motor Output (hp) 0.25 0.5 1.0
Rated Output Capacity (kVA) 0.6 1.0 1.6
Rated Output Current (A) 1.6 2.5 4.2
Maximum Output Voltage (V)
3-Phase Proportional to Twice the Input Voltage
Output Frequency (Hz)
0.1~600 Hz
Output Rating
Carrier Frequency (kHz)
2-12
Rated Input Current (A) 6.4 9 18
Rated Voltage/Frequency Single phase, 100-120V, 50/60Hz
Voltage Tolerance
±
10%(90~132 V)
Input Rating
Frequency Tolerance
±
5%(47~63 Hz)
Cooling Method Natural Cooling
Weight (kg) 1.1 1.1 1.4
Voltage Class 230V Class
Model Number VFD-XXXEL 002 004 007 015 022 037
Max. Applicable Motor Output (kW) 0.2 0.4 0.75 1.5 2.2 3.7
Max. Applicable Motor Output (hp) 0.25 0.5 1.0 2.0 3.0 5.0
Rated Output Capacity (kVA) 0.6 1.0 1.6 2.9 4.2 6.5
Rated Output Current (A) 1.6 2.5 4.2 7.5 11.0 17
Maximum Output Voltage (V)
3-Phase Proportional to Input Voltage
Output Frequency (Hz)
0.1~600 Hz
Output Rating
Carrier Frequency (kHz)
2-12
Rated Input Current
(A)
4.9 6.5 9.5 15.7 24 --
XXXEL
21A
Rated
Voltage/Frequency
1-phase, 200-240 V, 50/60Hz
Rated Input Current
(A)
1.9 2.7 4.9 9 15 20.6
XXXEL
23A
Rated
Voltage/Frequency
3-phase, 200-240V, 50/60Hz
Voltage Tolerance
±
10%(180~264 V)
Input Rating
Frequency Tolerance
±
5%(47~63 Hz)
Cooling Method Natural Cooling Fan Cooling
Weight (kg) 1.2 1.2 1.2 1.7 1.7 1.7