Delta Electronics VFD-EL Power Supply User Manual


 
Chapter 4 Parameters|
4-48 Revision August 2008, 2ELE, V1.02
Settings Function Description
14
Heat Sink Overheat
Warning
When heatsink overheats, it will signal to prevent OH turn off
the drive. When it is higher than 85
o
C (185
o
F), it will be ON.
15 Over Voltage supervision
Active when the DC-BUS voltage exceeds level
16 PID supervision
Active when the PID feedback signal is abnormal (Refer to
Pr.10.12 and Pr.13.)
17 Forward command
Active when the direction command is FWD
18 Reverse command
Active when the direction command is REV
19
Zero Speed Output
Signal
Active when the drive is standby or stop
20
Communication Warning
(FbE,Cexx, AoL2, AUE,
SAvE)
Active when there is a Communication Warning
21
Brake Control (Desired
Frequency Attained)
Active when output frequency Pr.03.11. Deactivated when
output frequency Pr.03.12 after STOP command.
22 AC Motor Drive Ready
Active when AC motor drive is ready.
03.01
Reserved
03.02 Desired Frequency Attained Unit: 0.01
Settings 0.00 to 600.0 Hz Factory Setting: 0.00
If a multi-function output terminal is set to function as Desired Frequency Attained (Pr.03.00
=09), then the output will be activated when the programmed frequency is attained.