Chapter 4 Parameters|
4-64 Revision August 2008, 2ELE, V1.02
01011 0
Weights
Bit
0=external terminal
1=internal terminal
MI1
MI2
MI3
MI4
MI5
MI6
This parameter is used to set the internal terminal action via keypad or communication.
For standard AC motor drive, the multi-function input terminals are MI1 to MI6 as shown in the
following.
12345 0
0=set internal terminal to be OFF
1= ONset internal terminal to be
MI1
MI2
MI3
MI4
MI5
MI6
Weights
Bit
For example, if setting MI3, MI5 and MI6 to be ON, Pr.04.28 should be set to
bit5X2
5
+bit4X2
4
+bit2X2
2
= 1X2
5
+1X2
4
+1X2
2
= 32+16+4=52 as shown in the following.
01011 0
Weights
Bit
0=OFF
1=ON
MI1
MI2
MI3
MI4
MI5
MI6
04.28
Internal Terminal Status
Unit: 1
Settings
0 to 4095
Factory Setting: 0