Emerson Network Router Network Router User Manual


 
28 ProLink
®
II Software for Micro Motion
®
Transmitters
Installation and Setup
To make the software connection from ProLink II to your transmitter.
1. Ensure that your PC is connected to the transmitter, according to one of the methods described
in Section 2.2.5.
2. Start ProLink II software.
3. From the
Connection menu, click on Connect to Device.
4. Specify connection parameters:
•Use the
Protocol parameter to specify your connection type. For HART/Bell 202
connections using the VIATOR USB HART Interface, enable
Converter Toggles RTS.
•Set
Serial Port to the PC COM port you are using to connect to the transmitter.
If you are making a service port or HART/Bell 202 connection, default values are used for
all remaining connection parameters.
If you are connecting to MVD Direct Connect, set the remaining connection parameters to
any of the supported settings listed in Table 2-13.
For all other connection types:
- For Model 2400S transmitters, set the address to the Modbus address configured for
your transmitter.
Note: Due to the transmitter’s auto-detection feature, other connection parameters are not required.
- For all other transmitters, set the remaining connection parameters to the values
configured in your transmitter.
Table 2-16 Default communication parameters for RFT97xx and IFT97xx transmitters
Default values
Transmitter Physical layer Protocol Baud Data bits
(1)
(1) ProLink II automatically sets data bits appropriately for the configured protocol. Even though a data bits parameter may be
configured in the transmitter, you do not need to configure it in ProLink II.
Stop bits Parity Address
IFT9701/9703
(2)
(2) IFT9701/9703 communication parameters are not configurable. The settings shown here are always in effect.
Bell 202
(3)
(3) Connection to primary mA output.
HART 1200 8 1 odd 0
RFT9712 Bell 202
(3)
HART 1200 8 1 odd 0
RS-485
(4)
(4) Connection to RS-485 terminals.
HART 1200 8 1 odd 0
RFT9739 v2 Bell 202
(3)
HART 1200 8 1 odd 0
RS-485
(4)
HART 1200 8 1 odd 0
RFT9739 v3 Bell 202
(3)
HART 1200 8 1 odd 0
RS-485
(4)(5)
(5) Dip switch settings on the transmitter are used to select either Std. comm or User defined.
• Std. comm Modbus RTU 9600 8 1 odd 1
• User defined HART 1200 8 1 odd 0