Automatic Voltage Regulation (AVR) Function
The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a
relatively constant amplitude during power input fluctuations. This can be useful if the
installation is subject to input voltage fluctuations. However, the inverter cannot boost its
motor output to a voltage higher than the power input voltage. If you enable this feature,
be sure to select the proper voltage class setting for your motor.
“A” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
A081 AVR function select Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00 .. AVR enabled
01 .. AVR disabled
02 .. AVR enabled except
during deceleration
✘ ✘ 00 00
AVR Mode ON
A082 AVR voltage select 200V class inverter settings:
...... 200/215/220/230/240
400V class inverter settings:
...... 380/400/415/440/460/480
✘ ✘ 230/
400
230/
460
V
AVR AC 00230V