Hitachi L2002 Power Supply User Manual


 
L2002 Inverter
Appendix B
B–33
Note 1: When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored (for A092/A292 and A093/A293).
A152 Pot. input active range
end frequency
R/W The output frequency corre-
sponding to the potentiometer
range ending point,
range is 0.0 to 400.0
1097h 4247 0 to 4000 0.1 Hz
A153 Pot. input active range
start current
R/W The output frequency corre-
sponding to the potentiometer
range starting point,
range is 0 to 100
1098h 4248 0 to 100 1%
A154 Pot. input active range
end current
R/W The output frequency corre-
sponding to the potentiometer
range ending point,
range is 0 to 100
1099h 4249 0 to 100 1%
A155 Pot. input start
frequency enable
R/W Two options:
00... Disable
01... Enable
109Ah 4250 0, 1
Holding Registers for “A” Group Standard Functions
Func.
Code
Name R/W Description
Network Data
Register
Range Res.
hex dec.