Hitachi L2002 Power Supply User Manual


 
“P” Group: Expansion Card Functions
Configuring
Drive Parameters
3–64
“P” Group: Expansion Card Functions
The (optional) expansion card for the L2002 inverter has assiciated configuration data.
The following table defines the functions and their value ranges. Please refer to the
expansion card manual for more details.
NOTE: The “P” Group parameters do not appear in the parameter list shown on the
keypad display unless the expansion card is installed on the inverter.
“P” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
P044 Network comm
watchdog timer
Range is 0.00 to 99.99 ✘ ✘ 1.00 1.00 sec.
TIMER 01.00s
P045 Inverter action on
network comm error
Five options:
00... Trip (Error Code E70)
01... Decelerate to stop and trip
(Error Code E70)
02... Hold last speed
03... Free run stop
04... Decelerate and stop
✘ ✘ 01 01
T-OUT FTP
P046 Polled I/O output
instance number
Three settings:
20, 21, 100
✘ ✘ 21 21
O-AS-INS 021
P047 Polled I/O input
instance number
Three settings:
70, 71, 101
✘ ✘ 71 71
O-AS-INS 071
P048 Inverter action on
network idle mode
Five options:
00... Trip (Error Code E70)
01... Decelerate to stop and trip
(Error Code E70)
02... Hold last speed
03... Free run stop
04... Decelerate and stop
✘ ✘ 01 01
IDLE FTP
P049 Network motor poles
setting for RPM
Range is 00 to 38 (even
numbers only)
✘ ✘ 00
P 00P