Hitachi L2002 Power Supply User Manual


 
L2002 Inverter
Configuring
Drive Parameters
3–31
ADD Frequency – The inverter can add or subtract an offset value to the output
frequency setting which is specified by A001 (will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter A145. The ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function A146 selects whether to add or subtract. By config-
uring an intelligent input as the [ADD] terminal, your application can selectively apply
the fixed value in A145 to offset (positively or negatively) the inverter output frequency
in real time.
A001
Function F001 setting
Control terminal
Network variable F001
Calculate function output
Keypad potentiometer
A145
+
+/–
ADD frequency
Frequency source setting
Output frequency setting
[ADD]Intelligent input
A146
ADD direction select
“A” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
A145 ADD frequency An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
✔ ✔ 0.0 0.0 Hz
ST-PNT 0000.0Hz
A146 ADD direction select Two options:
00 .. Plus (adds A145 value to
the output frequency setting)
01 .. Minus (subtracts A145
value from the output
frequency setting)
✘ ✔ 00 00
ADD DIR PLUS
A151 Pot. input active range
start frequency
The output frequency corre-
sponding to the potentiometer
range starting point,
range is 0.0 to 400.0
✘ ✔ 0.0 0.0 Hz
POT EXS 0.0
A152 Pot. input active range
end frequency
The output frequency corre-
sponding to the potentiometer
range ending point,
range is 0.0 to 400.0
✘ ✔ 0.0 0.0 Hz
POT EXE 0.0
A153 Pot. input active range
start current
The output frequency corre-
sponding to the potentiometer
range starting point,
range is 0.0 to 100.0
✘ ✔ 0.0 0.0 %
POT EX%S 0.0