Hitachi L2002 Power Supply User Manual


 
ModBus Data Listing
Appendix B
B–34
The following table lists the holding registers for the “B” Group Fine Tuning Functions.
“B” Group Fine Tuning Functions
Func.
Code
Name R/W Description
Network Data
Register
Range Res.
hex dec.
B001 Selection of automatic
restart mode
R/W Select inverter restart method,
four option codes:
00... Alarm output after trip,
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.
10A5h 04261 0, 1, 2, 3
B002 Allowable under-
voltage power failure
time
R/W The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
10A6h 04262 3 to 250 0.1 sec
B003 Retry wait time before
motor restart
R/W Time delay after under-
voltage condition goes away,
before the inverter runs motor
again.
Range is 0.3 to 100 seconds.
10A7h 04263 3 to
1000
0.1 sec
B004 Instantaneous power
failure / under-voltage
trip alarm enable
R/W Two option codes:
00... Disable
01... Enable
10A8h 04264 0, 1
B005 Number of restarts on
power failure / under-
voltage trip events
R/W Two option codes:
00... Restart 16 times
01... Always restart
10A9h 04265 0, 1
B012 Level of electronic
thermal setting
R/W Set a level between 20% and
120% for the rated inverter
current
10AD
h
04269 2000 to
12000
0.01%
B212 Level of electronic
thermal setting, 2nd
motor
R/W 1526h 05414
B013 Electronic thermal
characteristic
R/W Select from two curves,
option codes: *1
00... Reduced torque 1
01... Constant torque
02... Reduced torque 2
10AEh 04270 0, 1, 2
B213 Electronic thermal
characteristic, 2nd
motor
R/W 1527h 05415