Hitachi L2002 Power Supply User Manual


 
ModBus Data Listing
Appendix B
B–40
C041 Overload level setting R/W Sets the overload signal level
between 0% and 200% (from
0 to two times the rated
current of the inverter)
1124h 04388 0 to
20000
0.01 %
C042 Frequency arrival
setting for acceleration
R/W Sets the frequency arrival
setting threshold for the
output frequency during
acceleration, range is 0.0 to
400.0 Hz
1126h 04390 0 to 4000
*1
0.1 Hz
C043 Arrival frequency
setting for deceleration
R/W Sets the frequency arrival
setting threshold for the
output frequency during
deceleration, range is 0.0 to
400.0 Hz
1128h 04392 0 to 4000 0.1 Hz
C044 PID deviation level
setting
R/W Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%
1129h 04393 0 to 1000 0.1 %
C052 PID FBV function high
limit
R/W When the PV exceeds this
value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%
112Eh 04398 0 to 1000 0.1 %
C053 PID FBV function low
limit
R/W When the PV goes below this
value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%
112Fh 04399 0 to 1000 0.1 %
C071 Communication speed
selection
NOTE: These network
settings are not accessible to
ModBus. Use the inverter
keypad or digital operator to
edit. Refer to
“Network
Communication Settings
on page 3–58.
1138h 04408
C072 Node allocation 1139h 04409
C074 Communication parity
selection
113Bh 04411
C075 Communication stop bit
selection
113Ch 04412
C076 Communication error
select
113Dh 04413
C077 Communication error
time-out
113Eh 04414
C078 Communication wait
time
113Fh 04415
“C” Group Intelligent Terminal Functions
Func.
Code
Name R/W Description
Network Data
Register
Range Res.
hex dec.