L2002 Inverter
Configuring
Drive Parameters
3–63
“H” Group: Motor Constants Functions
The “H” Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values to
match the motor. Parameter H006 is factory-
set. If you want to reset the parameters to the
factory default settings, use the procedure in
“
Restoring Factory Default Settings” on
page 6–8. Use A044 to select the torque
control algorithm as shown in the diagram.
NOTE: If you are using automatic torque boost (A041/A241 = 01) and the output
current is unstable in the low frequency range, be sure to adjust A042/A242 and
A043/A243 with H006/H206 in order to decrease the boost voltage as an addition to the
standard V/f curve.
Output
A44
V/f control,
constant torque
V/f control,
variable torque
00
01
Inverter Torque Control Algorithms
“H” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
H003 Motor capacity Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
✘ ✘ Specified by the
capacity of each
inverter model
kW
AUX K 0.4 kW
H203 Motor capacity, 2nd
setting
Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11
✘ ✘ kW
2AUXK 0.4 kW
H004 Motor poles setting Four selections:
2 / 4 / 6 / 8
✘ ✘ 4 4 poles
AUX P 4p
H204 Motor poles setting, 2nd
motor
Four selections:
2 / 4 / 6 / 8
✘ ✘ 4 4 poles
2AUXP 4p
H006 Motor stabilization
constant
Motor constant (factory set),
range is 0 to 255
✔ ✔ 100 100 —
AUX KCD 100
H206 Motor stabilization
constant, 2nd motor
Motor constant (factory set),
range is 0 to 255
✔ ✔ 100 100 —
2AUXKCD 100