Hitachi L2002 Power Supply User Manual


 
L2002 Inverter
Operations
and Monitoring
4–17
Set Second Motor and Special-Set Second Motor
If you assign the [SET] or [S-ST] function to an intelligent input terminal, you can select
between two sets of motor parameters. The second parameters store an alternate set of
motor characteristics. Two type of inputs are available:
Set Second Motor - The inverter can select a different motor only in Stop Mode.
Special-Set Second Motor - The inverter can select a different motor in either Stop
Mode or Run Mode. The following parameter pairs can be alternately selected during
Run Mode: A020/A220, F002/F202, F003/F203, A042/A242, A043/A243, A061/
A261, A062/A262, A092/A292, A093/A293, A094/A294, A095/A295, A096/A296
When the terminal [SET] or [S-ST] is turned ON, the inverter will use the second set of
parameters to generate the frequency output to the motor. When changing the state of the
[SET] input terminal, the change will not take effect until the inverter is stopped.
When you turn ON the [SET] or [S-ST] input, the inverter operates per the second set of
parameters. When the terminal is turned OFF, the output function returns to the original
settings (first set of motor parameters). Refer to
Configuring the Inverter for Multiple
Motors” on page 4–58 for details.
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
08 SET Set (select) 2nd
Motor Data
ON causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor. The selection of 1st or 2nd motor is
available only in Stop Mode.
OFF causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
53 S-ST Special-Set (select)
2nd Motor Data
ON causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor. The selection of 1st or 2nd motor is
available in Stop Mode or Run Mode.
OFF causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
Valid for inputs:
C001, C002, C003, C004,
C005
Required settings:
(none)
Notes:
If the terminal state for [SET] is changed while the
inverter is running, the inverter continues using the
current set of parameters until the inverter is
stopped.
You cannot configure the inverter to use [SET] and
[S-ST] terminals at the same time.
Example (requires input configuration—see
page 3–47
):
See I/O specs on page 4–6
.
12345L
PCS
SET
(or S-ST)