Hitachi L2002 Power Supply User Manual


 
“C” Group: Intelligent Terminal Functions
Configuring
Drive Parameters
3–48
The input logic convention is programmable for each of the five inputs. Most inputs
default to normally open (active high), but you can select normally closed (active low) in
order to invert the sense of the logic.
C004 Terminal [4] function Select terminal [4] function,
29 options (see next section)
✘ ✘
03
[CF2]
13
[USP]
IN-TM 4 USP
C204 Terminal [4] function,
2nd motor
Select terminal [4] function,
29 options (see next section)
✘ ✘
03
[CF2]
13
[USP]
2IN-TM 4 USP
C005 Terminal [5] function Select terminal [5] function,
30 options (see next section)
✘ ✘
18
[RS]
09
[2CH]
IN-TM 5 2CH
C205 Terminal [5] function,
2nd motor
Select terminal [5] function,
30 options (see next section)
✘ ✘
18
[RS]
09
[2CH]
2IN-TM 5 2CH
“C” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
“C” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
C011 Terminal [1] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘ ✘ 00 00
O/C-1 NO
C012 Terminal [2] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘ ✘ 00 00
O/C-2 NO
C013 Terminal [3] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘ ✘ 00 00
O/C-3 NO
C014 Terminal [4] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘ ✘ 00 01
O/C-4 NC
C015 Terminal [5] active state Select logic convention, two
option codes:
00... normally open [NO]
01... normally closed [NC]
✘ ✘ 00 00