Hitachi L2002 Power Supply User Manual


 
L2002 Inverter
Configuring
Drive Parameters
3–47
“C” Group: Intelligent Terminal Functions
The five input terminals [1], [2], [3], [4], and [5] can be configured for any of 19
different functions. The next two tables show how to configure the five terminals. The
inputs are logical, in that they are either OFF or ON. We define these states as OFF=0,
and ON=1.
The inverter comes with default options for the five terminals. These default settings are
initially unique, each one having its own setting. Note that European and US versions
have different default settings. You can use any option on any terminal, and even use the
same option twice to create a logical OR (though usually not required).
NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a
thermistor device when the PTC function (option code 19) is assigned to that terminal.
Input Terminal Configuration
Functions and Options –The function codes in the following table let you assign one of
nineteen options to any of the five logic inputs for the L200
2 inverters. The functions
C001through C005 configure the terminals [1] through [5] respectively. The “value” of
these particular parameters is not a scalar value, but it is a discrete number that selects
one option from many available options.
For example, if you set function C001=00, you have assigned option 00 (Forward Run)
to terminal [1]. The option codes and the specifics of how each one works are in
Chapter 4.
“C” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
C001 Terminal [1] function Select terminal [1] function,
29 options (see next section)
✘ ✘
00
[FW]
00
[FW]
IN-TM 1 FW
C201 Terminal [1] function,
2nd motor
Select terminal [1] function,
29 options (see next section)
✘ ✘
00
[FW]
00
[FW]
2IN-TM 1 FW
C002 Terminal [2] function Select terminal [2] function,
29 options (see next section)
✘ ✘
01
[RV]
01
[RV]
IN-TM 2 RV
C202 Terminal [2] function,
2nd motor
Select terminal [2] function,
29 options (see next section)
✘ ✘
01
[RV]
01
[RV]
2IN-TM 2 RV
C003 Terminal [3] function Select terminal [3] function,
29 options (see next section)
✘ ✘
02
[CF1]
16
[AT]
IN-TM 3 AT
C203 Terminal [3] function,
2nd motor
Select terminal [3] function,
29 options (see next section)
✘ ✘
02
[CF1]
16
[AT]
2IN-TM 3 AT