Hitachi L2002 Power Supply User Manual


 
L2002 Inverter
Inverter Mounting
and Installation
2–19
Please use the terminal arrangement below corresponding to your inverter model.
NOTE: An inverter powered by a portable power generator may receive a distorted
power waveform, overheating the generator. In general, the generator capacity should be
five times that of the inverter (kVA).
Inverter models L200–002NFEF2/NFU2, –004NFEF2/NFU2,
–005NFEF2
Inverter models L200–007NFEF2 to –022NFEF2,
–037LFU2, –004HFEF2/HFU2 to –040HFEF2/HFU2
Jumper
Chassis
Ground
U
/T1
V
/T2
W
/T3
Inverter models L200–055LFU2, –055HFE2/HFU2,
–075LFU2, –075HFE2/HFU2
+
L1 L2
N/L3
+1
Jumper
Chassis
Ground
U/T1
+1 +
L1 L2 N/L3
NFEF, NFU
LFU, HFEF, HFU
V/T2
W/T3
U/T1
V/T2
W/T3R/L1
S/L2
T/L3
+1 +
Jumper
Chassis Ground
Inverter models L200–055HFEF2, –075HFEF2
U/T1
L1 L2
V/T2
W/T3
L3
PD/+1
N/–
Jumper
U/T1
V/T2
W/T3
Chassis Ground
R/L1 S/L2 T/L3
P/+