255
Receiving Explicit Messages Section 9-2
Operating mode: Returns the operating mode of the CPU Unit in 1-byte
(2-digit) hexadecimal.
0001 Hex: PROGRAM mode; 0002 Hex: MONITOR mode;
0004 Hex: RUN mode
Fatal error information: Returns the fatal error information for the CPU
Unit in 2 bytes (low to high).
Non-fatal error information: Returns the non-fatal error information for
the CPU Unit in 2 bytes (low to high).
76543210Bit
Unspecified
Flash memory access status (CS1H, CJ1-H, CJ1M, and CS1D only)
0: Memory is not being written.
1: Memory is being written.
Operation status
0: Stopped (User program is not being executed.)
1: Operating (User program is being executed.)
CPU status
0: Normal
1: CPU standb
y
(
waitin
g
for SYSMAC Bus Remote I/O or other event
)
Battery status (CS1H, CJ1-H, CJ1M, and CS1D only)
0: No battery
1: Battery installed
----
1: System error (FALS)
1: Cycle time over
1: Program error
1: I/O setting error
1: No. of I/O points exceeded
1: Inner Board fatal error
1: Number duplicate use error
1: I/O Bus error
1: Memory error
Unspecified (reserved for system use)
1: Special I/O Unit error
1: CPU Bus settings error
1: Battery error
1: SYSMAC BUS error
1: Special I/O Unit
1: CS1-series CPU Bus Unit error
1: Inner Board error
1: I/O verification error
1: PLC system error
1: Unspecified (reserved for system use)
1: Basic I/O Unit error
1: Interrupt task error
1: Unspecified (reserved for system use)
1: S
y
stem error
(
FAL
)