Sun Microsystems CP3260 Server User Manual


 
5-16 Netra CP3260 Blade Server User’s Guide April 2009
Temperature Monitoring
The ADM1026 also monitors the CPU diode temperature on the Netra CP3260 blade
server. The ADM1206 and H8 firmware reports a minor, major, or critical alarm
when the temperature of the CPU goes beyond the thresholds listed in
TABLE 5-2.
Also, if the temperature of the CPU goes beyond the Emergency H8 Shutdown
value listed in
TABLE 5-2, the H8 initiates a event/warning blade server to the shelf
manager and shuts down.
TABLE 5-1 Voltage Sensor Thresholds
Sensor
Number
Sensor
Name Voltage
ADM1026 Generated
Critical Warning
(approx. 7%)
H8 Initiated Shutdown
(approx. 10%)
Lower Upper Lower Upper
7 12.0V 12V 11.16V 12.84V 11V 13.2V
8 5.0V 5V 4.8V 5.2V 4.78V 5.23V
9 3.3V 3.3V 3.07V 3.53V 3V 3.6V
10 3.3V STBY 3.3V 3.07V 3.53V 2.97V 3.63V
11 3V VBAT/STBY 3V 2.79V No UC no
shutdown
no
shutdown
12 1.0V 1V 0.93V 1.07V 0.9V 1.1V
13 1.1V CPU 1.1V 1.02V 1.18V 0.99V 1.21V
14 VDD 1.1V 1.1V 1.02V 1.18V 0.99V 1.21V
15 1.5V 1.5V 1.4V 1.61V 1.35V 1.65V
16 VDD 1.8V 1.8V 1.67V 1.93V 1.62V 1.98V
17 VDD 2.5V 2.5V 2.37V 2.68V 2.36V 2.75V
18 VDD_IO 1.2V 1.5V 1.4V 1.61V 1.35V 1.65V
TABLE 5-2 CPU Temperature Alarms
Sensor
Number
Sensor
Name
Minor Alarm
(UNC)
Major Alarm
(UC)
Critical Alarm
(UNR)
Emergency
H8 Shutdown
4 CPU Temp 1 >80° C >90° C > 102° C > 102° C
5 CPU Temp 2 >80
° C >90° C > 102° C > 102° C
6 Board Temp >60
° C >70° C>88° C>88° C