108 4200FA Installation and Operation Manual
TOSHIBA 4200FA UPS
Installation Planning Guide for 15-50kVA UPS
208/120V Input, 208/120V Output
For Maximum cable sizes, see Note 6 & 7.
General Mechanical Information
UPS kVA/ kW Rating
Dimensions
(W x D x H)
Weight
w/o Battery (w/ Battery)
Approximate Full-Load
Heat Loss
Inches Lbs. kBtu/Hr
15 kVA/12 kW
20 x 36.3 x 60
618 (724)
5.8
25 kVA/ 20 kW
20 x 36.3 x 60
628 (734)
8.3
30 kVA/ 24 kW
20 x 36.3 x 60
633 (739)
11.7
50 kVA/ 40 kW
35.6 x 37.9x 59.7
1221 (2,548)
18.1
Primary AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External Feeder
Breaker
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
>0.97
42
60 A
(1) x 6 / (1) x 4
380
25
>0.97
67
90 A
(1) x 3 / (1) x 1
380
30
>0.97
81
110 A
(1) x 2 / (1) x 1
380
50
>0.97
138
175 A
(1) x 2/0 / (1) 250
380
External Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Feeder Breaker
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet
15
14
61
70 A
(1) x 4
70
25
23
100
100 A
(1) x 1
70
30
28
120
125 A
(1) x 1
70
50
45
195
200 A
(1) x 250
70
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
Suggested External Feeder
Breaker
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
15
0.8
42
60 A
(1) x 6 / (1) x 4
380
25
0.8
69
90 A
(1) x 3 / (1) x 1
380
30
0.8
83
110 A
(1) x 2 / (1) x 1
380
50
0.8
139
175 A
(1) x 2/0 / (1) 250
380