Toshiba 4200FA Power Supply User Manual


 
116 4200FA Installation and Operation Manual
Blk Item Long Description
Short Description
(Inside UPS)
Units
Permissions
Remark
RE
III
User Admin
1 12 Input Frequency (C) Freq (C) dHz R R 600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
Y
1 21 Input Voltage in % (A) Voltage (A) % R R Percentage of Line to Line and Line
to Neutral Voltage are the same
Y
1 22 Input Voltage in % (B) Voltage (B) % R R Percentage of Line to Line and Line
to Neutral Voltage are the same
Y
1 23 Input Voltage in % (C) Voltage (C) % R R Percentage of Line to Line and Line
to Neutral Voltage are the same
Y
1 40 No of Input Lines No of Input Line R R Y
1 41 Rated Line to Line Input Voltage Rated Voltage L-L V R R Y
1 42 Rated Line to Neutral Input Voltage Rated Voltage L-N V R R Y
1 43 Rated Input Current Rated Current A R R Y
1 45 Rated Input Power (W) Rated Power (W) W R R Y
1 46 Rated Input Power (VA) Rated Power (VA) VA R R Y
1 47 VIUV Detection Level VIUV DeLevel % R R Y
1 49 VIOV Detection Level VIOV DeLevel % R R Y
1 58 Enable Phase Check En Phase Check R R Y
2 1 Output Line to Line Voltage (AB) Voltage (AB) V R R Y
2 2 Output Line to Line Voltage (BC) Voltage (BC) V R R Y
2 3 Output Line to Line Voltage (CA) Voltage (CA) V R R Y
2 4
Output Line to Neutral Voltage (AN)
Voltage (AN) V R R Y
2 5
Output Line to Neutral Voltage (BN)
Voltage (BN) V R R Y
2 6
Output Line to Neutral Voltage (CN)
Voltage (CN) V R R Y
2 7 Output Phase Current (A) Current (A) A R R Y
2 8 Output Phase Current (B) Current (B) A R R Y