Toshiba 4200FA Power Supply User Manual


 
4200FA Installation and Operation Manual 23
Table 6.4 Bypass Wire Size
Minimum / Maximum Wire Size and Torque Requirements
UPS Optional Separate Bypass Input TB4 15 / 25kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
15 kVA 25 kVA 30 kVA
AWG* Torque AWG* Torque AWG* Torque
208 V 8 – 1 51 in-lbs. 4 – 1 51 in-lbs. 2 – 1 87 in-lbs.
220 V 8 – 1 51 in-lbs. 4 – 1 51 in-lbs. 2 – 1 87 in-lbs.
240 V 8 – 1 51 in-lbs. 4 – 1 51 in-lbs. 2 – 1 87 in-lbs.
380 V 10 – 1 35 in-lbs. 8 – 1 51 in-lbs. 6 – 1 51 in-lbs.
400 V 10 – 1 35 in-lbs. 8 – 1 51 in-lbs. 6 – 1 51 in-lbs.
415 V 10 – 1 35 in-lbs. 8 – 1 51 in-lbs. 6 – 1 51 in-lbs.
480 V 10 – 1 35 in-lbs. 8 – 1 51 in-lbs. 6 – 1 51 in-lbs.
600 V 10 – 1 35 in-lbs. 10 – 1 35 in-lbs. 10 – 1 35 in-lbs.
*Maximum Wire Size is 1 AWG.