Toshiba 4200FA Power Supply User Manual


 
18 4200FA Installation and Operation Manual
5 Installation Precautions
Based on the 4200FA UPS external dimensions and the way the outer panels are removed;
minimum amounts of unobstructed space around the unit are necessary for ventilation and
maintenance access. The following section and Fig. 3.1 shows the minimum clearances required for
proper UPS site installation.
Equipment Placement 5.1
Do not install the UPS on an inclined surface, or
areas that are subject to frequent vibrations
or jolting. This could damage UPS circuits.
Do not allow liquids or foreign objects to get
inside the UPS.
Allow at least the following spacing for air
ventilation and maintenance access.
Front: 20 in. (500 mm)
Sides: 6 in. (152 mm)
Back:
15-30kVA Premium - 6 in. (152 mm)
15-30kVA Base - 12 in. (304 mm)
50kVA Premium - 12 in. (304 mm)
25/50kVA Seismic - 12 in. (304 mm)
Do not install the UPS in a location that is subject
to high humidity. Also, do not install the unit in areas that are exposed to direct sunlight, or
contaminated areas subject to high levels of airborne dust, metal particles, or flammable
gasses.
Verify the ventilation and air conditioning system at the site is capable of removing the heat
generated by the UPS.
Ambient temperature range for operating the UPS is 32 104 °F (0 40 °C);
77 °F (25 °C) is the recommended operating temperature for maximum battery life.
Avoid installation near sources of electrical noise. Always make sure that the unit's ground is
intact to prevent electrical shock and help prevent electrical noise.
This UPS generates and radiates radio-frequency energy during operation. Although RFI noise
filters are installed inside the unit there is no guarantee that the UPS will not influence some
sensitive devices, which are operating in near proximity. If such interference occurs, the
UPS should either be installed farther away from the affected equipment and/or powered
from a different source than the affected equipment.
FRONT
20 in. (500 mm)
REAR
15-30 kVA Premium 6 in. (152 mm)
15-30 kVA Base – 12 in. (304 mm)
50 kVA Premium – 12 in. (304 mm)
25/50 kVA Seismic 12 in. (304 mm)
LEFT
6 in.
(152 mm)
RIGHT
6 in.
(152 mm)