Toshiba 4200FA Power Supply User Manual


 
34 4200FA Installation and Operation Manual
6.4.1 Recommended Wire Size and Torque Requirements
UPS Control and Battery Interface 50 kVA wire and torque requirements.
Table 6.12 TB-3 Tightening Torque
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75 °C COPPER WIRING
TERMINAL
(TERMINAL #)
50 kVA
AWG*
TIGHTENING
TORQUE
UPS CONTROL CIRCUITS
(1-24)*
14-16 8 in-lbs.
BATTERY CONTROL
CIRCUITS (3-6)*
14-16 8 in-lbs.
*Indicates Class 1 wiring methods are to be used. Maximum Wire Size is 12 AWG.