Toshiba 4200FA Power Supply User Manual


 
4200FA Installation and Operation Manual 117
Blk Item Long Description
Short Description
(Inside UPS)
Units
Permissions
Remark
RE
III
User Admin
2 9 Output Phase Current (C) Current (C) A R R Y
2 10 Output Frequency (A) Freq (A) dHz R R 600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
Y
2 11 Output Frequency (B) Freq (B) dHz R R 600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
Y
2 12 Output Frequency (C) Freq (C) dHz R R 600 for 60.0 Hz, 500 for 50.0 Hz.
UPS will send you one decimal
point and format it according to
decimal points
Y
2 13 Output Power W (Total) Power W (Total) kW R R Y
2 21 Output Voltage % (A) Voltage % (A) % R R Percentage of Line to Line and Line
to Neutral Voltage are the same
Y
2 22 Output Voltage % (B) Voltage % (B) % R R Percentage of Line to Line and Line
to Neutral Voltage are the same
Y
2 23 Output Voltage % (C) Voltage % (C) % R R Percentage of Line to Line and Line
to Neutral Voltage are the same
Y
2 24 Output Current % (Total) Current % (Total) % R R Y
2 25 Output Current % (A) Current % (A) % R R Y
2 26 Output Current % (B) Current % (B) % R R Y
2 27 Output Current % (C) Current % (C) % R R Y
2 28 Output Power W % (Total) Power W % (Total) % R R Y
2 36 Output Power Factor Power Factor R R Y
2 40 No of Output Line No of Output Line R R Y
2 41 Rated Line to Line Output Voltage Rated Voltage L-L V R R Y
2 42 Rated Line to Neutral Output Voltage Rated Voltage L-N V R R Y