APC AP7900 Computer Accessories User Manual


 
®
USER’S GUIDE
Switched Rack PDU
154
Contents of the .ini file
The config.ini file that you retrieve from a Switched Rack PDU contains the
following:
section headings, which are category names enclosed in brackets ([ ]),
and under each section heading, keywords, which are labels
describing specific Rack PDU settings.
Each keyword is followed by an equals sign and the current value for
that parameter’s setting, either the default value (if the value has not
been specifically configured) or the configured value.
The Override keyword, with its default value, prevents one or more
keywords and their device-specific values from being exported. In the
[NetworkTCP/IP] section, the default value for Override (the MAC
address of the Rack PDU) blocks the exporting of the values for the
keywords SystemIP, SubnetMask, DefaultGateway, and
BootMode.
You must edit the section [SystemDate/Time] if you want to set the
system date and time of a receiving Rack PDU or cause that Rack PDU
to use an NTP Server to set its date and time.
Only section headings and keywords supported for the
specific device associated with the Rack PDU from which you
retrieve the file are included.
See Customizing for configuration guidelines for date
and time settings.