21000, you would use the following command for a Windows FTP
client transferring a file to a Rack PDU with an IP address of
150.250.6.10.
ftp> open 150.250.6.10 21000
4. Log on using the Administrator user name and password. (apc is the
default for both.)
5. Upgrade the AOS. For example:
ftp> bin
ftp> put apc_hw02_aos_264.bin
6. When FTP confirms the transfer, type Quit to close the session.
7. Wait 20 seconds, and then repeat step 2 through step 6, but in step 5, use
the application module file name instead of the AOS module.
Instructions for using SCP. To use Secure CoPy (SCP) to upgrade the
firmware for one Rack PDU:
1. Identify and locate the firmware modules described in the preceding
instructions for FTP.
2. Use an SCP command line to transfer the AOS firmware module to the
Rack PDU. The following example assumes a Rack PDU IP address of
158.205.6.185, and an AOS module of apc_hw02_aos_264.bin.)
scp apc_hw02_aos_264.bin apc@158.205.6.185:apc_hw02_aos_264.bin
3. Use a similar SCP command line, with the name of the application
module instead of the AOS module, to transfer the application module
to the Rack PDU.
How to upgrade multiple Rack PDUs
Export configuration settings. You can create batch files and use an
APC utility to retrieve configuration settings from multiple Rack PDUs and
export them to other Rack PDUs.