APC AP7900 Computer Accessories User Manual


 
®
USER’S GUIDE
Switched Rack PDU
46
Switched Rack PDU Settings
Configure Load Thresholds
Web interface.
1. Select Switched Rack PDU from the navigation menu.
2. Click Configure in the Load Management section.
3. Set Overload Alarm Threshold, Near Overload Warning Threshold,
Low Load Warning Threshold, and Overload Outlet Restrictions
for each phase or bank.
4. Click Apply in that section to set the selected values.
Control console.
1. From the Device Manager menu, select Phase/Bank Monitor/
Configuration.
2. Select a phase or bank (for 3-phase units).
3. Select Overload Alarm Threshold (amps), Near Overload Warning
Threshold (amps), or Low Load Warning Threshold (amps).
4. Select Accept Changes.
To set the overload outlet restriction, select
Outlet Restriction Configuration
on the Device manager menu. For 3-phase units, select a phase or bank to
display and change the Outlet Phase/Bank Restriction.
Setting Description
Overload Alarm
Threshold
Set the number of amps that will cause an overload of this phase
or bank.
Near Overload
Warning Threshold
Set the number of amps at which to generate a warning that the
Rack PDU is nearing overload of a phase or bank.