Baldor MN1851 Tablet User Manual


 
3-6 Receiving & Installation MN1851
Figure 3-5 Single Phase AC Power Connections (LP1AxxT & LP2AxxT only)
L1 L2
Alternate *
Fuse
Connection
Note 1
L1 L2
LN
* Circuit
Breaker
Earth
Note 2
Note 1
Baldor
Control
Notes:
1. See Protection Devices described in this section.
2. Metal conduit or shielded cable should be used. Connect
conduits so the use of a Reactor or RC Device does not
interrupt EMI/RFI shielding.
3. Use same gauge wire for Earth ground as is used for L and N.
(VDE (Germany) requires 10mm
2
minimum, 6AWG). For CE
Compliance, connect to the backplane of the enclosure.
4. Reference EMC wiring in Section 8.
Note 3 & 4
* Components not provided with Control.
For CE Compliance, refer to Section 8 of this manual.
Figure 3-6 Single Phase AC Power Connections (LP1AxxS only)
L1 L2
Alternate *
Fuse
Connection
Note 1
L1 L2
PE
* Circuit
Breaker
Earth
Note 2
Note 1
Baldor
Control
Notes:
1. See Protection Devices described in this section.
2. Metal conduit or shielded cable should be used. Connect
conduits so the use of a Reactor or RC Device does not
interrupt EMI/RFI shielding.
3. Use same gauge wire for Earth ground as is used for L and N.
(VDE (Germany) requires 10mm
2
minimum, 6AWG). For CE
Compliance, connect to the backplane of the enclosure.
4. Reference EMC wiring in Section 8.
Note 3 & 4
L1 L2 L3
* Components not provided with Control.
For CE Compliance, refer to Section 8 of this manual.
Note: These Lin+Drive versions are not designed for use with 400/460VAC
connections.