Baldor MN1851 Tablet User Manual


 
Command Set B-3MN1851
Startup with Terminal Communication and Command Examples
1. Select the correct COM port NR. and set the following at your PC:
Baud Rate: 9600
Protocol (Hardware, Xon/Xoff, None): OFF
Data Length: 8 Bit
Stop Bit: 1
Parity: NONE
2. Set the control address. The address is set by switch AS1-1 to AS1-4.
To locate a control, type A then the control address, e.g. A3 (searches
for a control with address 3). If a drive with address 3 is running and
connected to the PC COM, this drive answers with the prompt sign > to
indicate that communication to the drive is established. Additional
command may be sent to the A3 control.
Entering an address command with another address number, will
terminate communication with control A3. If more than one drive is
connected to the PC COM port, typing the address of another drive
connected, will change communication path to this one.
3. Communication is now established and the ASCII commands may be
used.
Note: If more than one drive is connected to the PC port, correct communication
can only be established if all drives have different addresses.
4. Error messages (from the control)
If the syntax and the values of the ASCII command string are correct, the
control accepts the command and answers by sending < as
acknowledge. If any error within the transferred command was found,
the control rejects the command by sending a correlated error string.
There are following terminalreported errors :
SYNTAX ERROR: invalid character;
EXECUTION ERROR: invalid command;
RANGE ERROR: invalid parameter value;
INVALID EXE CONTEXT: invalid command or operation mode;
control DESIGN FAILURE: invalid control design;
INPUT BUFFER OVERFLOW: command line exceeded 80 char.;
TOO MANY PARAMETERS: too many parameters;
REQ. PARAMETER MISSED: not enough parameters;
In case of an error, the event protocol will return a NAK ( negative
acknowledge ) to a user. The error check can only provide a syntax and
range check for each command. Error checking will not check a wrong
parameter value that may degrade system performance.