Troubleshooting
Troubleshooting 6-1MN1851
Overview
The system troubleshooting procedures involve observing the status of the
Ready LED, the DB On LED and the Monitor 7 segment display. The tables
in this section provide information related to the indications provided by these
devices.
Note: The Ready LED can display RED, YELLOW or GREEN color.
Table 6-1 Operating Mode Indications
Ready Monitor Status Cause
OFF OFF Control Disabled No Fault.
Green Decimal
Point
Control Enabled Normal operating mode. No Fault.
Red 1 Over-voltage fault (DC Bus) Missing, damaged or wrong REGEN resistor.
Input voltage too high.
Red 3 Over-current fault.
(More than 2X peak current)
Motor leads shorted or control failure.
Load exceeds motor rating (too much
current).
Accel time set too short.
Red 4 Over or Under-voltage fault. Internal 15VDC supply fault.
Red 5 Encoder fault (or encoder fault). Encoder or cable short circuit or encoder not
connected (open circuit).
Red 6 Electronic fusing
(also see fault 7)
Control current over-load detected by
software.
Red 7 I
2
t limit reached. After a fault is detected,
control will run at nominal output current for
2.5 seconds then stop. The control is disabled
and the Monitor will first display 7 fault then
the 6 fault.
Control Over-Temperature
Cycle time between Acceleration and
Deceleration is too short.
Control should be relocated to cooler area.
Add fans or air conditioning to control
cabinet.
Red 9 User defined fault (see PLC).
Red 0 Processor Watchdog timeout Reset control (turn off AC power, wait 1
minute then turn power on).
Green
Move Command not accepted. More than two move commands have been
sent to the control. To return to normal
status, send a Quit or a new move
command to the control.
A non-initialized buffer line has been called
by the Machine inputs. To return to normal
status, call an initialized buffer line by
MA1-4 or send a Quit to the control.
Green -l CW Enable switch activated. CW limit reached. Check X3-10 input.
Green l- CCW Enable switch activated. CCW limit reached. Check X3-11 input.
Note: To protect the internal fuse, allow at least 1 minute after power down before
turning power on (power Off/On cycle).