Dell FC830 Laptop User Manual


 
Environmental specifications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation
orientations).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six
sides tested).
Maximum shock
Operating Six consecutively executed shock pulses in the
positive and negative x, y, and z axes of 40 G for
up to 2.3 ms.
Storage Six consecutively executed shock pulses in the
positive and negative x, y, and z axes (one pulse
on each side of the system) of 71 G for up to 2
ms.
Maximum altitude
Operating
3048 m (10,000 ft).
Storage 12,000 m (39,370 ft).
Operating temperature de-rating
Up to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300 m
(1°F/547 ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F) Maximum temperature is reduced by 1°C/175 m
(1°F/319 ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1°C/125 m
(1°F/228 ft) above 950 m (3,117 ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental conditions will be the
responsibility of the customer.
Air filtration
NOTE: Applies to data center environments
only. Air filtration requirements do not
apply to IT equipment designed to be used
outside a data center, in environments such
as an office or factory floor.
Data center air filtration as defined by ISO Class 8
per ISO 14644-1 with a 95% upper confidence
limit.
NOTE: Air entering the data center must
have MERV11 or MERV13 filtration.
Conductive dust
NOTE: Applies to data center and non-data
center environments.
Air must be free of conductive dust, zinc whiskers,
or other conductive particles.
130