Emerson 4015 Power Supply User Manual


 
IM584000300 Installation Instructions
Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)
Page 22 Chapter 3. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 3-6
Sub-Rack Interconnections
Load Distribution Sub-Rack DC Input Cables
(Factory connected in load distribution sub-rack,
customer to route into power and control
sub-rack and connect to power and control
sub-rack DC output terminals.)
Battery Tray Output Cables
(Factory connected in battery tray,
customer to route into power and
control sub-rack and connect to
power and control sub-rack battery
terminals.)
Rear
Load
Distribution
Sub-Rack
Power and
Control
Sub-Rack
Battery
Tray
*Note: Battery cables can also be
routed through the bottom of the
power and control sub-rack.
Battery Terminals
for 400V DC Battery Strings
(five sets of 1/4-20 x 5/8
studs on 5/8centers for
double hole lugs,
each polarity)
Rear View
(covers removed)
Negative
Battery*
Positive
Battery*
++
--
(Recommended
Torque: 84 in-lbs
[9 Nm])
Power and
Control
Sub-Rack
(Recommended
Torque: 84 in-lbs
[9 Nm])
400V DC Output Terminals
(two sets of 1/4-20 x 5/8
studs on 5/8centers for
double hole lugs,
each polarity)
Negative
Output
Positive
Output