Emerson 4015 Power Supply User Manual


 
IM584000300 Installation Instructions
Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)
Page 46 Chapter 5. Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
VERIFYING THE CONFIGURATION FILE
For factory configured systems, your ACU+ was programmed with a configuration file that
sets all adjustable parameters. The version number of the configuration file can be found
on the configuration drawing (C-drawing) that is supplied with your power system
documentation, and on a label located on the ACU+. You can verify that the correct
configuration file has been loaded into your ACU+ by performing the following procedure.
Procedure
Note: When viewing any of the following screens, if a key is not depressed within
approximately 10 seconds, the ACU+ will automatically return to the Main screen.
1) With the Main screen displayed, press ESC. A screen displays the serial number
and software version.
2) Press ENT. A screen displays the hardware version and MAC address.
3) Press ENT. A screen displays the configuration version number.
4) Press ESC, or wait approximately 10 seconds, to return to the Main screen.
CHANGING BATTERY CAPACITY RATING IN THE ACU+
To change the battery capacity setting of the ACU+ to match the battery connected to the
power system, perform the following procedure.
Procedure
1) With the Main screen displayed, press ENT to go to the Main Menu. Navigate to
and select Settings” (ENT).
2) If a password screen opens, a password must be entered to allow the User to
make adjustments. If a password was previously entered and has not yet timed
out, skip this step and proceed to step 3). Otherwise, to enter a password, with
the cursor at the User Name field (default is “Admin”), press the down arrow key
to move cursor down to the password line. Press ENT. “0” is highlighted. Press
the up arrow key once to change the “0” to”1” (default password is “1”), then
press ENT twice. (Note: If you have been assigned a unique User Name and
password, follow this procedure to enter these.)
3) With the Settings menu screen displayed, navigate to and select Battery” (ENT)
/ “Basic (ENT).
4) Navigate to Rated Capacity”. Press ENT. Use the up or down keys to adjust
the value as required. Press ENT.
Note: For NetSure 4000 Series Battery Tray's, the capacity value is 8.5 A-hr per
tray. For customer provided batteries, enter the C10 battery capacity
rating in A-hr.
5) Return to the Main screen by repeatedly pressing ESC (escape).