IM584000300 Installation Instructions
Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)
Page 48 Chapter 5. Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Parameter
Menu Navigation
Date
Main Menu / Settings / Controller / Date
Time
Main Menu / Settings / Controller / Time
IP Communications Parameters
(IP address, subnet mask address,
gateway address)
Main Menu / Settings / Communication
Float Voltage
Main Menu / Settings / Battery / Charge / Operating Voltage
Equalize Voltage
Main Menu / Settings / Battery / Charge / Batt EQ Voltage
Battery Capacity
Main Menu / Settings / Battery / Basic / Rated Capacity
BTRM Feature
Main Menu / Settings / Battery / Basic / BTRM Action
Main Menu / Settings / Battery / Basic / BTRM Voltage
Temperature Compensation
Center Temperature
Main Menu / Settings / Battery / Temp Comp / TempComp Center
Temperature Compensation Slope
Main Menu / Settings / Battery / Temp Comp / TempComp Coeff
Maximum Temperature
Compensation Voltage
Main Menu / Settings / Battery / Temp Comp / Max TempComVolt
High Voltage Shutdown Limit
Main Menu / Settings / Rectifier / All Rect Set / HVSD Limit
Over Voltage Alarm
Main Menu / Settings / Power System / General / Over Voltage
Under Voltage Alarm
Main Menu / Settings / Power System / General / Under Voltage
Table 5-1
Basic Settings Local Menu Navigation