Emerson 4015 Power Supply User Manual


 
IM584000300 Installation Instructions
Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)
Page 44 Chapter 5. Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
ACU+ CONTROLLER INITIALIZATION
Note: For factory configured systems, your controller was programmed with a
configuration file that sets all adjustable parameters. Provided on a USB drive
furnished with the system is an ACU+ configuration drawing (C-drawing) and the
ACU+ configuration files loaded into the ACU+ as shipped. If ordered for
customer integration, you will have to program the controller for your application
per step 8) below.
Refer to the ACU+ Controller Operation Instructions (UM1M820NNB-1) for detailed
instructions.
Refer to Figure 5-2 for locations of the ACU+ local indicators and navigation keys.
Figure 5-2
ACU+ Controller Local Indicators and Navigation Keys
Procedure
Note: The initialization routine takes several minutes. During that time various alarm
indicators may illuminate on the ACU+ front panel and an audible alarm may
sound. Disregard all alarms. An audible alarm can be silenced at any time by
momentarily depressing the ENT key on the ACU+ Controller.
1) After the ACU+ is powered on, the display alternates between the “Emerson
Network Power” screen and a screen displaying “Advanced Control Unit Plus
Version ***** Starting….
ESC ENT
Menu Navigation Keys
USB Port
10/100M Ethernet
Port (RJ-45)
Status
Indicator
(Green)
Information Alarm
Indicator (Yellow)
Warning or Critical
Alarm Indicator
(Red)