Installation Instructions IM584000300
Spec. No. 584000300 (Model 4015-X003) Issue AB, April 3, 2013
Chapter 5. Initially Starting the System Page 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
INITIALLY STARTING THE SYSTEM
Procedure
1) Close the external AC disconnect or protective device that supplies AC power to
the system.
2) Place each rectifier module AC input circuit breaker located on the front of the
power and control sub-rack to the ON position. Rectifiers automatically start.
3) Place each internal battery tray circuit breaker to the ON position. Place each
external battery string circuit breaker to the ON position.
4) Place each distribution row input circuit breaker located on the load distribution
sub-rack to the ON position (if furnished).
5) Place each load distribution circuit breaker located on the load distribution sub-
rack to the ON position.