Chapter 5. Initially Starting the System Page 45
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
2) Next, the language screen appears. Press the up or down arrow key to select
the desired language. Press the ENT key to confirm the selection. If no key is
pressed within 10 seconds, the ACU+ selects the displayed language
automatically.
3) As initialization continues, the Main screen is displayed, but with zero volts.
Initialization is not complete.
4) When initialization is complete, the Main screen displays voltage and current
normally, and no alarms are active.
5) System information is displayed in multiple screens. Repetitively press the up or
down arrow key to view other system information screens one by one.
6) From the Main screen, press ENT to go to the “Main Menu” screen.
7) From the Main Menu, select a sub-menu by repetitively pressing the up or down
arrow key. The selected sub-menu will be indicated by the cursor. Press ENT to
open the sub-menu.
Note: Repeatedly press the “ESC” key to return in reverse order level by level from
any sub-menu until the Main screen appears.
8) Verify and set the ACU+ Controller as required for your application. Refer to the
ACU+ Controller Operation Instructions (UM1M820NNB-1) for procedures. Note
that you will have to program the ACU+ for any temperature probes and external
inputs/outputs connected to the IB2 Interface Board, and battery capacity if
different then the factory default of 8.5 Ah (8.5 Ah per internal battery tray).