Fujitsu M400R Computer Hardware User Manual


 
CHAPTER 6 M600 Main Cabinet
Installation specifications
Table 6.5 Installation Specifications of M600 Main Cabinet (1)
Item Specification
Mass Up to 250kg (approx.552 lb) (*1)
Power condition Input voltage
Single phase
100 to 120 VAC
(+-10%)
Single phase
200 to 240 VAC
(+-10%)
Input frequency
50/60 Hz (+2 to -4%)
Maximum consumption current 13.4 A
Leakage current (1 for each cable) 2.2 mA or less
6.6 A
4.7 mA or less
Ground resistance 100ohm or less ( class C installation standard)
Temperature condition Operating 5 to 35 degrees Celsius (+41 to +95 F) (*2)
Not operating 0 to 50 degrees Celsius (+32 to +122F)
Humidity condition Operating 20 to 80%RH (no condensation)
Not operating 8 to 80% RH (no condensation)
Vibrations condition Operating 0.2 G
Idle 0.4 G
Noise 55 db (A) (*3)
Installation Floor Stand type
*1: The mass shows M600 main cabinet without Expansion File Units.
*2: If the ambient temperature exceeds 35 degrees Celsius (+95 F) during operation, a
warning message is output. Take steps to rectify the problem immediately.
*3: The indicated noise is the mean value of the measurements obtained in an anechoic
chamber with less echoic influence. The actual noise measured at the installation site
may be greater than the indication noise due to surrounding noise and echoes.