Fujitsu M400R Computer Hardware User Manual


 
CHAPTER 2 M200 Main Cabinet
IMPORTANT
If the above conditions are not satisfied, the M200 main cabinet may be damaged. Be sure
to follow these precautions.
Installation specifications
Table 2.3 Installation Specifications of M200 Main Cabinet (1)
Item Specification
Mass Up to 43kg (approx.94.9 lb)
Power condition Input voltage
Single phase
100 to 120 VAC
(+-10%)
Single phase
200 to 240 VAC
(+-10%)
Input frequency
50/60 Hz (+2 to -4%)
Maximum consumption current 5.0 A
Leakage current 3.5 mA or less
2.5 A
3.5 mA or less
Ground resistance 100ohm or less ( class C installation standard)
Temperature condition Operating 5 to 35 degrees Celsius (+41 to +95 F) (*1)
Not operating 0 to 50 degrees Celsius (+32 to +122F)
Humidity condition Operating 20 to 80%RH (no condensation)
Not operating 8 to 80% RH (no condensation)
Vibrations condition Operating 0.2 G
Idle 0.4 G
Noise 47 db (A) (*2)
Installation standalone type
*1: If the ambient temperature exceeds 35 degrees Celsius (+95 F) during operation, a
warning message is displayed. Take steps to rectify the problem immediately.
*2: The indicated noise is the mean value of the measurements obtained in an anechoic
chamber with less echoic influence. The actual noise measured at the installation site
may be greater than the indication noise due to surrounding noise and echoes.
24