Installing the Plenum (if required)
If installing one of the following SAN switches only, you must install the plenum that
ships in the accessory kit with the rack mount hardware:
• 4/8 SAN Switch
• 4/16 SAN Switch
• 4/32B SAN Switch
To install th
eplenum:
1. Place the device (with inner rails attached) on a flat surface, see Figure 17.
2. Obtain the plenum and four 8-32 x .312 Phillips Pan-head SEMs screws from the
accessory kit.
3. For each in
ner rail (Left and Right)useonescrewholemarked8 and one screw
hole marked 16 to attach the plenum.
CAUTION:
Verify that the open end of the plenum faces the rear of the switch. For example, when
installe
d properly you should see the plenum’s air vent holes on one side, and the front
panel of the switch on the other.
SAN Switch installation guide
49