Omron NT631C Printer User Manual


 
216
Programming Console Function Section 6-12
CQM1: @@@3, @@@4, @@@5, @@*6
where * is a number in the range 1 to 9 or the letter X or Y.
C200HX/HG/HE: @@@5 @@*6
where * is a number in the range 1 to 9 or the letter X or Y.
6-12-2 Connection Method
CQM1, CQM1H, C200HX/
HG/HE(-Z)E, or SRM1
The connection method is exactly the same as for the NT Link (1:1). Refer to
SECTION 4 Connecting to the Host from the RS-232C Port or SECTION 5
Connecting to the Host from the RS-422A/485 Port for details on connecting
to the PLC.
* When using the Programming Console function with a CQM1H, turn ON pin
7 of the DIP switch on the front of the CQM1H’s CPU Unit.
CPM1 or CPM2A The connection method is the same as for the NT Link (1:1). With a CPM1,
connect the RS-232C cable to the peripheral port via a CPM1-CIF01 RS-
232C Adapter or CPM1-CIF11 RS-422A Adapter.
Refer to SECTION 4 Connecting to the Host from the RS-232C Port or SEC-
TION 5 Connecting to the Host from the RS-422A/485 Port for details on con-
necting to the PLC.
CPM2C The connection method is the same as for the NT Link (1:1). Connect to the
PLC’s communications connector with a CPM2C-CN111 or CS1W-CN114/
118 Connecting Cable, a CPM1-CIF01 RS-232C Adapter, or a CPM1-CIF11
RS-422A Adapter.
Refer to SECTION 4 Connecting to the Host from the RS-232C Port or SEC-
TION 5 Connecting to the Host from the RS-422A/485 Port for details on con-
necting to the PLC.
* When using the Programming Console function with a CPM2C, turn ON pin
2 of the DIP switch on the front of the CPM2C’s CPU Unit.
CS/CJ-series PLC The connection method is exactly the same as for the NT Link (1:N) (standard
or high-speed). Refer to SECTION 4 Connecting to the Host from the RS-
232C Port or SECTION 5 Connecting to the Host from the RS-422A/485 Port
for details on connecting to the PLC. The standard or high-speed 1:N NT Link
can be used.
The Programming Console function can be used only when the PT’s unit num-
ber is set to 0. Only one Unit using the Programming Console function can be
connected to each of the PLC’s ports (built-in RS-232C port and peripheral
port).
Make sure that the PT’s highest unit number is set to 0 in the CS/CJ-series
PLC setup.
With the CS/CJ-series PLC, the Programming Console function can not be
used simultaneously at both the built-in RS-232C port and peripheral port.
Furthermore, the Programming Console function can not be started at the
RS-232C port while a Programming Console is connected to the peripheral
port.