Omron NT631C Printer User Manual


 
48
Connecting to the RS-232C Port at the Host Section 4-1
4-1 Connecting to the RS-232C Port at the Host
The method for connecting between the RS-232C port of the PT and the RS-
232C port of the host is as follows.
The following discussion is focused on the connection method to OMRON
PLCs (By using the memory link method, a connection can be made to any
arbitrary RS-232 unit). When making a connection to a host other than
OMRON PLCs, refer to the PLC Connection Manual (V042-E1-@) or NT31/
631 Multi Vendor Connection Manual (V060-E1-@).
Direct Connection Between The RS-232C Ports Using an RS-232C Cable
(page 73)
This is the easiest connection method. Depending on the host to which the
connection is to be made, it may be possible to use OMRON cables with con-
nectors.
Reference: The CS/CJ-series CPU Unit cannot be connected with the 1:1 connection NT
Link method. Use the 1:N connection NT Link method instead to make the 1:1
connection. For details, refer to Using the NT Link (1:N) Method (page 65) or
Using the High-speed NT Link (1:N) Method (page 70).
4-1-1 Host Types and Settings
The types of host that can be connected to a PT by using the RS-232C ports
of both Units, and the settings to be made at the host, are described here.
When Using the Host Link
Method
Compatible Host Units
Some models and series of OMRON PLCs have the host link function built in.
In the CS/CJ-series or CQM1H PLCs, the host link method can be used by
installing a Serial Communications Board/Unit. In addition, some C200HX/
HG/HE(-Z)E CPU Unit can be connected in the host link method by installing
a Communications Board.
Check the model and series of the PLC, the type of installed Serial Communi-
cations Board, Serial Communications Unit, or Host Link Unit before making a
connection.
The hosts that can be connected to the NT631/NT631C by the host link
method using the RS-232C ports of both Units are indicated in the table
below.
RS-232C cable (max. 15 m)
Host
NT631/NT631C
PLC
Series
Units with Built-in Host Link
Function
CPU Units Connectable with
Host Link Units or Expansion
Communications Board/Units
Host Link Unit or
Communications
Board/Unit
Connect-
able to
CS Series CS1G-CPU42/43/44/45-E(V1)
CS1H-CPU63/64/65/66/67-E(V1)
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
CS1D-CPU65H/67H
CS1G-CPU42/43/44/45-E(V1)
CS1H-CPU63/64/65/66/67-E(V1)
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
CS1D-CPU65H/67H
(*1)
CS1W-SCU21(-V1)
CS1W-SCB21(-V1)
CS1W-SCB41(-V1)
CS1G
CS1H
CS1D
CJ Series CJ1G-CPU44/45
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1M-CPU11/12/13/22/23
CJ1G-CPU44/45
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1M-CPU11/12/13/22/23
CJ1W-SCU21(-V1)
CJ1W-SCU41(-V1)
CJ1G
CJ1H
CJ1M