Omron NT631C Printer User Manual


 
52
Connecting to the RS-232C Port at the Host Section 4-1
C1000H/C2000H Rack-mounting Unit: C500-LK203
Setting the Rear Switches
C200H/C1000H/C2000H CPU-mounting Unit: 3G2A6-LK201-EV1
Setting the Rear Switches
ON
ON
SW1
SW2
I/O port
RS-422A
RS-232C
Synchronization
Internal
External
Terminator
OFF
ON
CTS
0 V
External
I/O port selection (selector switch)
Set this to RS-232C.
Synchronization (selector switch)
Set this to Internal.
Communications speed
(DIP SW2-1 to SW2-4)
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
Instruction level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
5 V supply
ON
OFF
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to OFF (0).
CTS selection (selector switch)
Set this alwa
y
s to 0 V
(
ON
)
.
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.(0: OFF 1: ON)
SW1
SW2
SW3
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to OFF (0).
Communications speed (DIP SW2-1 to SW2-4)
Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(0: OFF 1: ON)
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
Instruction level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
CTS selection (DIP SW3-1 and SW3-2)
Set SW3-1 to ON (1), and SW3-2 to OFF (0).
(Set this always to 0V.)
Synchronization (DIP SW3-3 to SW3-6)
* Parity is fixed at Even Parity. Transfer code is
fixed at ASCII 7 data bits and 2 stop bits.
Set SW3-3, SW3-5, and SW3-6 to ON (1), and
SW3-4 to OFF (0). (Set these to Internal.)