Toshiba 1600XP Power Supply User Manual


 
13
1600XP Series Installation and Operation Manual
UPS
Connections
Terminal Block
The following illustration is a detail view of the terminal block and wiring connections used for 208/240
volt units (see pages 65-66 for terminal block location).
* – If only one input line is hot, connect hot line to terminal 1 (L), and connect the Neutral line to terminal 2 (N).
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with a jumper wire. DO NOT jumper terminal 13 to 12 or
11. Factory Setting is 208Vac. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with a jumper wire. DO NOT jumper terminal 11 to 12 or
13. Use the jumper wire provided by Toshiba. DO NOT add any additional jumpers.